Battery Operated Combination Carbon
Monoxide & Photoelectric Smoke Alarm
Part Number CP9000
Model KN-COPE-D
This alarm uses photoelectric sensing technology. Leading authorities recommend
that both ionization and photoelectric smoke alarms be installed to help insure
maximum detection of the various types of fires that can occur within the home.
Ionization sensing alarms may detect invisible fire particles (associated with fast
flaming fires) sooner than photoelectric alarms. Photoelectric sensing alarms may
detect visible fire particles (associated with slow smoldering fires) sooner than
ionization alarms.
Architectural and Engineering
Specifications
The combination smoke and carbon monoxide alarm shall be Kidde Part Number
CP9000 (Model KN-COPE-D) or approved equal. It shall be powered by one 9V
battery. The temperature operating range shall be between 40°F and 100°F (4°C
and 38°C) and the humidity operating range shall be 10% - 95% relative humid
-
ity, non condensing.
The unit shall incorporate a photoelectric smoke sensor with nominal sensitivity of
2.5 +/- 0.95%/ft. The CO sensor shall be of a fuel cell design and shall meet the
sensitivity requirements of Underwriters Laboratories UL2034 Single and Multiple
Station Carbon Monoxide Detectors. The unit shall qualify for UL-approved word
-
ing on the package: “World’s Most Accurate Carbon Monoxide Alarm.”*
The combination alarm can be installed on the surface of any wall or ceiling fol
-
lowing the UL/NFPA/Manufacturer’s recommended placement guidelines. The unit
shall provide optional tamper resistance that deters removal of the unit from the
wall or ceiling. No additional pieces shall be required to activate this feature.
The alarm shall include a test button that will electronically simulate the pres
-
ence of smoke and CO and cause the unit to go into both modes of alarm. This
sequence tests the unit’s electronics to ensure proper operation. The CO sensor
will not alarm to levels of CO below 30 ppm and will alarm in the following time
range when exposed to the corresponding levels of CO.
70 ppm CO Concentration 60 – 240 minutes
150 ppm CO Concentration 10 – 50 minutes
400 ppm CO Concentration 4 – 15 minutes
The combination alarm shall have two methods of warning for danger: a piezo
-
electric horn that is rated at 85 decibels at 10 feet and a voice warning that identi-
fies the danger. For a CO incident, the horn will sound in the repetitive manner
– four (4) fast beeps, a short pause, four (4) fast beeps, a short pause. In between,
the unit will announce “Warning Carbon Monoxide!” After four minutes the
alarm/voice pattern will sound once every minute until the unit is reset, or the
CO eliminated. In a Smoke incident, the horn will sound in the repetitive man
-
ner – three (3) beeps, a pause, three (3) beeps, a pause. In between, the unit will
announce “Fire! Fire!” The unit shall incorporate 2 LED’s. A green LED will flash
every 30 seconds when in standby condition, every 16 seconds to indicate alarm
memory, and every 2 seconds to indicate the Hush“ mode is active. A red LED will
flash in unison with the sounder pattern. The unit shall include the Smart Hush™
feature that silences the unit for approximately 8 minutes if a nuisance alarm condi
-
tion occurs. The Green LED on the alarm will flash every 2 seconds while in Smart
Hush™ and will automatically reset itself. Smart Hush™ Feature also provides voice
Technical Specifications
Part Number: CP9000
Model: KN-COPE-D
Power Source:
9V battery
Smoke Sensor: Photoelectric
CO Sensor: Electrochemical
Audio Alarm: 85dB at 10ft
Temperature Range: 40˚F (4.4˚C) to 100˚F (37.8˚C)
Humidity Range: 10%-95% relative humidity,
non-condensing
Size: 5.79” in diameter x 1.85” depth
Weight: .7lb
Interconnects: No
Warranty: 10 year limited
1016 Corporate Park Drive
Mebane NC 27302
1-800-880-6788 www.Kidde.com
KL-CP9000 sheet rev. 04-2014
Distributed by:
annunciation of “Hush Mode Activated” when Smart Hush™ is activated
and “Hush Mode Cancelled” when the Hush cycle ends.
The unit shall also indicate a low battery warning utilizing each of the
following methods: a brief alarm chirp, the voice announcement of
“Low Battery!” The unit shall at a minimum meet the requirements of UL
2034, UL217, NFPA72, (chapter 11 2002 edition) The State of California
Fire Marshall, NFPA101 (One and two family dwellings) Federal Housing
Authority (FHA), Housing and Urban Development (HUD). It shall also
include a 10-year manufacturer’s limited warranty.
*Claim approved by UL, based on manufacturer’s reported testing.
Ordering Information
Ordering Pack Pack Dimensions Cartons/
Number UPC I 2 of 5 Config Qty (w x d x h inches) Weight Pallet
21010031 0-47871-10031-6 100-47871-10031-6 CLAM Cut Case (4 Units) 7.9 x 13.2 x 11.7 1.8 54