AC Wire-in Single and/or Multiple Station (up to 24 Devices) Ionization SmokeAlarm with SMART HUSHTMControl to temporarily silence nuisance alarms.Mod
Hush®mode: The red LED will illuminate for 1.5 seconds every 8 seconds, indicating the smoke alarm is in the Hush®mode.Testing: Test by pushing the T
6. MAINTENANCEALARM REMOVALIF TAMPER RESIST PIN HAS BEEN USED, REFER TO TAMPER RESIST LOCK-ING PIN IN SECTION 3 FOR PIN REMOVAL INSTRUCTIONS.To replac
The SAFETY LIGHT (model i12080 only) portion is powered by one (1) 9V alka-line battery. Under normal (standby) conditions, the battery should last a
CAUTION! USE ONLY LAMP SPECIFIED. USE OF A DIFFERENT LAMP MAYHAVE A DETRIMENTAL EFFECT ON THE SMOKE ALARM OR THE SAFETYLIGHT OPERATION.CLEANING YOUR
• Smoke alarms must be tested regularly to make sure the batteries and thealarm circuits are in good operating condition.• Smoke alarms cannot provide
awakened by the alarm sound, or to those who may be incapable of safelyevacuating the area unassisted.WHAT TO DO WHEN THE ALARM SOUNDS• Alert small ch
Smoke Detection – Where required by applicable laws, codes, or standards forthe specified occupancy, approved single- and multiple-station smoke alarm
FIVE YEAR LIMITED WARRANTYKIDDE Safety warrants to the original purchaser that the enclosed smoke alarm (butnot the battery) will be free from defects
This alarm detects products of combustion using the ionization technique. Itcontains 0.9 microcurie of Americium 241, a radioactive material (see sect
FIGURE 1FIGURE 2 FIGURE 3• Locate at least one alarm on every floor level.• Locate an alarm in every bedroom.• Locate an alarm in every room where ele
• Install Smoke Alarms on sloped, peaked or cathedral ceilings at or within 3ft(0.9m) of the highest point (measured horizontally). NFPA 72 states: “S
air supply ducts used for heating or cooling, ceiling or whole house ventilatingfans, or other high air flow areas.• Kitchens. Normal cooking may caus
• When mixing models which have battery backup (i12040, i12060, i12080,1275, 1276, 1285, 1296, PE120, PI2000, KN-COSM-IB, RF-SM-ACDC,HD135F, KN-COB-IC
1. Remove the trim ring from the back of the alarm by holding the trim ring andtwisting the alarm in the direction indicated by the “OFF” arrow on the
TAMPER RESIST LOCKING PIN: To make your smoke alarm tamper resistant, alocking pin has been provided with your alarm. Using this pin will help deterc
NOTE: DENSE SMOKE WILL OVERRIDE THE HUSH CONTROL FEATURE ANDSOUND A CONTINUOUS ALARM.CAUTION: BEFORE USING THE ALARM HUSH FEATURE, IDENTIFY THESOURCE