AC Wire-in Single and/or Multiple Station (up to 24 Devices) Ionization SmokeAlarm with HUSHTMControl to temporarily silence nuisance alarms.Models i1
Testing: Test by pushing the Test/Hush button on the cover and hold it down for a minimum of 5 seconds. This will soundthe alarm if the electronic ci
To replace the batteries or the lamp (models i12040A and i12080A only), removethe alarm from the trim ring by rotating the alarm in the direction of t
NOTE: WEEKLY TESTING IS REQUIRED! If the Safety Light appears dimduring regular testing, replace both batteries immediately.USE ONLY THE FOLLOWING 9
CLEANING YOUR ALARMYOUR ALARM SHOULD BE CLEANED AT LEAST ONCE A YEARTo clean your alarm, remove it from the mounting bracket as outlined in thebeginni
• If the alarm is located outside the bedroom or on a different floor, it may notwake up a sound sleeper.• The use of alcohol or drugs may also impair
time getting dressed or picking up valuables.• In leaving, don’t open any inside door without first feeling its surface. If hot, orif you see smoke se
shall be installed as follows: (1) In all sleeping rooms Exception: Smoke alarmsshall not be required in sleeping rooms in existing one- and two-famil
TEN YEAR LIMITED WARRANTYKidde warrants to the original purchaser that the enclosed smoke alarm (but not thebattery) will be free from defects in mate
This alarm detects products of combustion using the ionization technique. Itcontains 0.9 microcurie of Americium 241, a radioactive material (see sect
FIGURE 1FIGURE 2 FIGURE 3• Locate at least one alarm on every floor level.• Locate an alarm in every sleeping room.• Locate an alarm in every room whe
• Install Smoke Alarms on sloped, peaked or cathedral ceilings at or within 3ft(0.9m) of the highest point (measured horizontally). NFPA 72 states: “S
door to a kitchen, the door to a bathroom containing a tub or shower, forcedair supply ducts used for heating or cooling, ceiling or whole house venti
nect up to a total of 6 remote signaling devices and/or relay modules.• When mixing models which have battery backup (i12040, i12040A, i12060,i12060A,
MOUNTING INSTRUCTIONSCAUTION: THIS UNIT IS SEALED. THE COVER IS NOT REMOVABLE!1. Remove the trim ring from the back of the alarm by holding the trim r
TAMPER RESIST LOCKING PIN: To make your smoke alarm tamper resistant, alocking pin has been provided with your alarm. Using this pin will help deterc
This alarm has a low battery HUSH feature. If the alarm is sounding a low bat-tery warning chirp, you can silence this chirp for approximately 13 hour