A.C. Wire-in Single and/or Multiple Station (up to 24 Devices) IonizationSmoke Alarm with 9 Volt Battery Back Up and SMART HUSHTMControl totemporarily
The red LED has four modes of operation:Standby Condition: The red LED will flash every 30-40 seconds to indicate that the smoke alarm is operating pr
5. NUISANCE ALARMSSmoke alarms are designed to minimize nuisance alarms. Cigarette smoke willnot normally set off the alarm, unless the smoke is blow
This smoke alarm uses a 9V carbon zinc battery (alkaline and lithium batteriesmay also be used). A fresh battery should last for one year under normal
vacuuming through the openings around the perimeter of the alarm. The out-side of the alarm can be wiped with a damp cloth. After cleaning, reinstall
• The use of alcohol or drugs may also impair one’s ability to hear the smokealarm. For maximum protection, a smoke alarm should be installed in each
• In leaving, don’t open any inside door without first feeling its surface. If hot,or if you see smoke seeping through cracks, don’t open that door!
Smoke Detection – Are More Smoke Alarms Desirable? The required number ofsmoke alarms might not provide reliable early warning protection for those a
FIVE YEAR LIMITED WARRANTYKIDDE Safety warrants to the original purchaser that the enclosed smoke alarm (but notthe battery) will be free from defects
This alarm detects products of combustion using the ionization technique. Itcontains 0.9 microcurie of Americium 241, a radioactive material (see Sect
FIGURE 1FIGURE 2 FIGURE 3• Locate an alarm in every room where someone sleeps with the door closed.The closed door may prevent an alarm not located in
MOBILE HOME INSTALLATIONModern mobile homes have been designed and built to be energy efficient.Install smoke alarms as recommended above (refer to RE
3. INSTALLATION INSTRUCTIONSWIRING REQUIREMENTS• This smoke alarm should be installed on a U.L. listed or recognized junctionbox. All connections shou
• The maximum wire run distance between the first and last unit in an intercon-nected system is 1000 feet.• Figure 4 illustrates interconnection wirin
1. Remove the trim ring from the back of the alarm by holding the trim ring andtwisting the alarm counter-clockwise.2. After selecting the proper smok
8. Turn on the AC power. The green Power On Indicator should be lit when thealarm is operating from AC power. Confirm unit operation by pressing theTe
NOTE: Before activating the battery carrier tamper resistfeature, make sure a fresh battery is installed in the unitand that the battery carrier is pr